TV/SC-IR

744-0X1000-XXX

DOWNLOAD REQUEST QUOTE
The reverse-acting TV/SC-IR (Tube Valve/Instrument Enclosure) is designed to open on rising temperature to regulate the flow of cooling media to an enclosure. The thermal wax actuator end of the valve is installed into the wall of the instrument enclosure to continuously sense the ambient temperature within the enclosure. When the temperature rises above the valve's set-point, it will automatically modulate open to allow the injection of the cooling media. The valve will modulate closed again once the ambient temperature is within 10°F (5.6°C) of the open set-point. These economical valves are available with set points from 40°F to 210°F (4.4°C to 98.9°C).
The reverse-acting TV/SC-IR can regulate the flow of glycol, water, air or other cooling media to keep an enclosure cool via a vortex cooler to protect expensive analyzers and instrumentation from overheating.
  • Exclusive Thermoloid® thermal actuator
  • Stainless Steel body, fittings, spring & plug
  • Compact low mass - fast response
  • Corrosion resistant - long service life
  • Ram-type plug for reliable tight shut-off
  • Compatible with standard tubing and connections
  • Maintains enclosure temperature within specified range
  • Self-operating, no power or signal required
  • Eliminates danger of overheating and explosion hazard
  • Long service life
  • Unaffected by pressure variations
  • Quick and easy installation
Series TV/SC-IR
Description 1/2" TV/SC-IR-S-SS
Size 1/2" NPT
Length-in 10.5
Length-mm 267
Weight lb 1.2
Weight kg 0.6
Cv 0.9
Maximum Operating Pressure 200 PSIG (13.8 BAR)
Maximum Temperature Valve End 388°F (198°C)
Maximum Temperature Sensing End 150°F (66°C) over set-point limit 300ºF(149ºC)
Opening Temperature 40°F, 45°F, 50°F, 60°F, 70°F, 75°F, 85°F, 95°F, 100°F, 105°F, 110°F, 115°F, 120°F, 125°F, 130°F, 140°F, 150°F, 160°F, 170°F, 175°F, 180°F, 190°F, 200°F, 210°F (4.4°C, 7.2°C, 10°C, 15.6°C, 21.1°C, 23.9°C, 29.4°C, 35°C, 37.8°C, 40.6°C, 43.3°C, 46.1°C, 48.9°C, 51.7°C, 54.4°C, 60°C, 65.6°C, 71.1°C, 76.7°C, 79.4°C, 82.2°C, 87.8°C, 93.3°C, 98.9°C)
Closing Temperature Valve will close 10°F below the open temperature
Body Material Stainless Steel
Fittings Parker A-LOK or Swagelok
Isometric View Download
Front View Download
Top View Download
Side View Download

Write a review

Note: HTML is not translated!
    Bad           Good