DTV

326-000000-XXX

DOWNLOAD REQUEST QUOTE
The DTV is installed into the drain line such that the hot effluent passes over the thermal actuator of the DTV and this thermal actuator controls the cold water inlet port. If the hot effluent is above the specified set-point, the DTV opens to allow injection of cold water. As the hot effluent cools, the DTV automatically modulates to reduce the cold water inlet flow. At 10°F below the full open temperature, the cold water inlet is fully closed to conserve water. Since the DTV is open only when the effluent exceeds the specified set-point temperature, it conserves water by automatically turning off cold water when not needed.
  • Exclusive Thermoloid® thermal actuator
  • Rugged, clog resistant valve design
  • Install using standard pipe fittings and tools
  • Operates in any orientation
  • Modulates to conserve cooling water
  • Efficient tempering capacity limited only by cold water flow rate through DTV
  • Self-operating – no external power source required
  • Compliant with drain temperature limitations of plumbing codes
  • Prevents damage to PVC piping due to Over-temperature conditions
  • Minimizes water waste
  • Easy to install
  • Adaptable to almost any drain size
Series DTV
Description 3/4" DTV Valve (Brass)
Length-in 7.9
Length-mm 200
Weight lb 1.2
Weight kg 0.5
Cv 2
Maximum Inlet Water Pressure 125 PSIG (8.6 BAR)
Maximum Temperature 250°F (121°C)
Opening Temperature 120°F, 125°F, 130°F, 140°F (48.9°C, 51.7°C, 54.4°C, 60°C)
Closing Temperature Valve will close 10°F below the open temperature
SIZE NPT Cold Water Inlet 3/4"
SIZE NPT Drain Connection 1"
Body Material Brass
Seal Material PTFE
Isometric View Download
Front View Download
Top View Download
Side View Download

Write a review

Note: HTML is not translated!
    Bad           Good