After water flow is activated at the shower or eyewash, the outlet water temperature will reach 85°F (29°C) when hot water arrives at the mixing valve. The mixing valve then blends the hot and cold water to produce an output of 85°F (29°C) water.
OSHA and ANSI require all your emergency fixtures to provide tepid water for a minimum & continuous 15-minute cycle. Tepid is defined to be between 60°F (16°C) and 100°F (38°C). The Therm-O-Mix® WWM Tepid Delivery System can ensure your emergency equipment will meet these codes. Since the station does not require any electric power, it is suitable for explosion-proof environments and outdoor installations.The Therm-O-Mix WWM tepid water mixing valve is typically used in facilities with only hot and cold water supply to provide tepid water delivery to safety shower and face/eyewash stations.
- Cv = 10.0 Conforms to OSHA and ANSI recommendations
- Provides 85°F (29°C) tepid water from 3 GPM (11.4 L/min) to 25 GPM (113.7 L/min) with water inlet pressure of at least 40 PSIG (2.8 BAR)
- Compact, lightweight (under 15 lbs/6 kg) design easily supported by piping connections
- All components are in-line serviceable
- Easy to retrofit on existing shower or combination shower/eyewash stations
- Maintains constant 85°F (29°C) output
- All self-operating controllers - no power required
- Utilizes existing hot and cold water supply
- Optional durable, all weather version in high visibility LDPE enclosure available
Series | Therm-O-Mix® Station WWM |
Description | THERM-O-MIX® STATION/WWM-85°F |
Cv | 10 |
Weight | 15 lbs (6 kg) |
Outlet Flow Rate Max | 25 GPM (113.7 L/min) |
Outlet Flow Rate Min | 3 GPM (11.4 L/min) |
Minimum Inlet Water Pressure | 40 PSIG (2.8 BAR) |
Outlet Temperature | 85°F (29°C) |
Isometric View | Download |
Front View | Download |
Top View | Download |
Side View | Download |